Product name | EASYPELL 06 | EASYPELL 09 | EASYPELL 12 | EASYPELL 12T | EASYPELL 17T | |
---|---|---|---|---|---|---|
Product model | EPA06 | EPA09 | EPA12 | EPA12T | EPA17T | |
Heating rated power | kW A7 / W35 | 3,3-8,3 | 4,5-11,4 | 5,9-14,8 | 5,9-14,8 | 8,8-22,0 |
kW A-2 / W35 | 3,0-7,3 | 3,7-9,3 | 4,9-12,0 | 4,9-12,0 | 7,3-17,9 | |
kW A-7 / W35 | 2,7-6,4 | 3,4-8,2 | 4,5-10,6 | 4,5-10,6 | 6,7-15,8 | |
kW A7 / W55 | 3,7-7,4 | 5,2-10,2 | 6,6-13,2 | 6,6-13,2 | 8,1-20,4 | |
kW A-2 / W55 | 2,8-6,7 | 3,5-8,6 | 4,5-11,2 | 4,5-11,2 | 6,8-16,6 | |
kW A-7 / W55 | 2,5-5,9 | 3,1-7,6 | 4,1-9,8 | 4,1-9,8 | 6,2-14,6 | |
COP Range | A7 / W35 | 4,2-5,3 | 4,2-5,3 | 4,2-5,3 | 4,2-5,3 | 4,2-5,3 |
COP Range | A7 / W55 | 3,1-3,8 | 3,1-3,8 | 3,1-3,8 | 3,1-3,8 | 3,1-3,8 |
COP mixed (EN14.511) | W35 / W55 | 5,1 / 3,2 | 4,9 / 3,2 | 5,0 / 3,0 | 5,0 / 3,0 | 4,6 / 3,2 |
SCOP middle climate (EN14.825) | W35 / W55 | 4,7 / 3,5 | 4,5 / 3,5 | 4,6 / 3,4 | 4,6 / 3,4 | 4,7 / 3,6 |
Cooling rated power | kW A35 / W18 | 2,6-6,1 | 3,6-8,6 | 4,7-11,3 | 4,7-11,3 | 6,8-16,1 |
EER | A35 / W18 | 4,11 (56 Hz) | 3,83 (58 Hz) | 3,73 (54 Hz) | 3,72 (51 Hz) | |
ErP Level | 35°C / 55°C | A+++ / A++ | A+++ / A++ | A+++ / A++ | A+++ / A++ | A+++ / A++ |
ɳs heating | 35°C / 55°C | 183 / 136 | 181 / 137 | 183 / 132 | 183 / 132 | 185 / 139 |
Refrigerant | R290 | R290 | R290 | R290 | R290 | |
Power supply | 230V/1Ph/50Hz | 230V/1Ph/50Hz | 380V/3Ph/50Hz | 380V/3Ph/50Hz | 380V/3Ph/50Hz | |
Electrical input power | kW | 0,76-2,72 | 0,83-3,51 | 1,01-4,51 | 1,01-4,51 | 1,51-6,76 |
Diameter of pipe / Connector | mm / inch | DN25 / F1" | DN25 / F1" | DN25 / F1" | DN25 / F1" | DN25 / F1" |
Max pump water head | m | 9 | 9 | 9 | 9 | 12 |
Water flow | m³/h | 1,4 | 2,0 | 2,6 | 2,6 | 3,8 |
Sound pressure at 3m (A7/W35) | dB(A) | 34 | 33 | 35 | 34 | 35 |
Sound power level (A7/W35) | dB(A) | 58 | 57 | 60 | 59 | 60 |
Net Weight | kg | 108 | 120 | 138 | 138 | 170 |
Net Dimension (L/W/H) | mm | 1085×460×825 | 1085×460×965 | 1085×480×1065 | 1085×480×1065 | 1085x480x1378 |
Flow pipe height | mm | 598 | 601 | 909 | 909 | xx |
Return pipe height | mm | 128 | 131 | 103 | 103 | xx |
Operating ambient temp.range | °C | -25 to 43 | -25 to 43 | -25 to 43 | -25 to 43 | -25 to 43 |
DHW temperature | °C | 20 to 65 | 20 to 65 | 20 to 65 | 20 to 65 | 20 to 65 |
Heating temperature | °C | 20 to 70 | 20 to 70 | 20 to 70 | 20 to 70 | 20 to 70 |
Cooling temperature | °C | 7 to 35 | 7 to 35 | 7 to 35 | 7 to 35 | 7 to 35 |
CONDITIONS FOR INSTALLATION